Selection
Supplies - 400 V controllers
12
Network of several drives
12.5
12.5.4
L
12.5-4
EDS82EV903-1.0-11/2002
12.5.4 Supplies - 400 V controllers
Supplies in DC -bus connection - 400 V controllers 66
Supply terminal 1
9341 9342 9365 9343 9330,
8224,
453K4B
752K4B 9332,
9333,
8226,
8227,
753K4B,
903K4B
9328,
8222,
223K4B
8244,
9324,
302K4B
9331,
8225,
553K4B
9364 9322,
8242,
8211,
8212
8215,
402K4B
9329,
8223,
303K4B
8213,
8214
9326,
8246,
8217,
8218,
113K4B
9327,
8221,
153K4B
551K4B,
751K4B
9323,
8243
9325,
8245,
8216
9321,
8241
152K4B,
222K4B
552K4B
P
DC
[kW]
7.2 14.4 100 27.0 60.5 11.6 106.7 33.0 6.1 68.5 50.0 2.2 6.6 36.4 4.3 14.4 29.7 1.5 4.6 7.9 2.8 3.8 9.0
P
V
[kW]
0.1 0.2 0.4 0.4 1.1 0.3 2.4 0.6 0.1 1.5 0.2 0.1 0.2 0.8 0.1 0.4 0.4 0.1 0.1 0.3 0.1 0.1 0.2
Supply 2...n
9341 X
9342 X X
9365 48.2 70.8 81.8
9343 X X 21.8 X
9330, 8224, 453K4B 28.8 42.2 48.8 49.5 49.5
752K4B 5.2 7.6 8.8 8.9 8.9 9.5
9332, 9333, 8226, 8227,
753K4B, 903K4B
47.1 69.1 79.9 81.0 81.0 86.4 87.3
9328, 8222, 223K4B 14.1 20.7 24.0 24.3 24.3 25.9 26.2 27.0
9324, 8244, 302K4B 2.6 3.8 4.4 4.5 4.5 4.8 4.8 5.0 5.0
9331, 8225, 553K4B 28.8 42.2 48.8 49.5 49.5 52.8 53.4 55.0 55.2 56.0
9364 20.9 30.7 35.5 36.0 36.0 38.4 38.8 40.0 40.2 40.8 40.9
9322, 8242, 8211, 8212 0.9 1.3 1.5 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.8
8215, 402K4B 2.6 3.8 4.4 4.5 4.5 4.8 4.8 5.0 5.0 5.0 5.1 5.3 5.4
9329, 8223, 303K4B 14.1 20.7 24.0 24.3 24.3 25.9 26.2 27.0 27.1 27.5 27.6 29.1 29.4 29.8
8213, 8214 1.6 2.3 2.6 2.7 2.7 2.9 2.9 3.0 3.0 3.0 3.0 3.2 3.2 3.3 3.5
9326, 8246, 8217, 8218,
113K4B
5.2 7.6 8.8 8.9 8.9 9.5 9.6 9.9 9.9 10.1 10.1 10.7 10.8 10.9 11.7 11.8
9327, 8221, 153K4B 10.4 15.2 17.6 17.8 17.8 19.0 19.2 19.8 19.9 20.2 20.2 21.4 21.6 21.9 23.4 23.5 24.3
551K4B, 751K4B 0.5 0.8 0.9 0.9 0.9 0.9 0.9 1.0 1.0 1.0 1.0 1.1 1.1 1.1 1.2 1.2 1.2 1.2
9323, 8243 1.5 2.3 2.6 2.7 2.7 2.8 2,9 3.0 3.0 3.0 3.0 3.2 3.2 3.3 3.5 3.5 3.6 3.7 3.8
9325, 8245, 8216 2.6 3.8 4.4 4.4 4.4 4.7 4.8 4.9 5.0 5.0 5.0 5.3 5.4 5.5 5.8 5.9 6.1 6.2 6.3 6.5
9321, 8241 0.9 1.3 1.5 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.8 1.8 1.8 2.0 2.0 2.0 2.1 2.1 2.2 2.3
152K4B, 222K4B 1.1 1.7 1.9 2.0 2.0 2.1 2.1 2.2 2.2 2.2 2.2 2.3 2.4 2.4 2.6 2.6 2.7 2.7 2.8 2.8 3.0 3.1
552K4B 2.6 3.8 4.4 4.5 4.5 4.8 4.8 5.0 5.0 5.1 5.1 5.4 5.4 5.5 5.9 5.9 6.1 6.2 6.3 6.5 6.8 7.1 7.4
Howtousethetable: 1. Look under ”supply 1” from left to right until you find a controller connected to the network.
2. Look for more devices in the same column for the corresponding power P
DC
and add the powers until the required sum
power is reached. Every added devices must be supplied.
Empty fields Supply combinations not possi ble
X Parallel connection of regenerative power supply units not possible