Questions and Answers

  • J
    James DayAug 31, 2025
    What does earth fault mean on Lenze ESMD112L4TXA Inverter?
    • B
      Barbara JacksonAug 31, 2025
      If the Lenze Inverter indicates an earth fault, it could be due to: * A grounded motor phase: Inspect the motor and motor cable. * Excessive capacitive charging current of the motor cable: Use shorter motor cables with a lower charging current.
  • L
    Laura BrownAug 25, 2025
    Why Lenze DC Drives show earth fault?
    • D
      Deborah LandryAug 25, 2025
      An earth fault in Lenze DC Drives can occur if a motor phase is grounded, so you should check the motor and motor cable. It can also be due to excessive capacitive charging current of the motor cable, in this case use shorter motor cables with lower charging current.
  • S
    Susan CrosbyAug 25, 2025
    What to do if Lenze DC Drives have controller overtemperature?
    • A
      Alexandria OsbornAug 26, 2025
      If the controller has an overtemperature, it means the controller is too hot inside. To resolve this, reduce the controller load and improve cooling.
  • J
    Jeremy StanleyAug 26, 2025
    What to do if Lenze DC Drives show undervoltage on DC bus?
    • N
      njohnstonAug 26, 2025
      If Lenze DC Drives show undervoltage on the DC bus, it could be because the mains voltage is too low. Check the mains voltage.
  • D
    Deborah HarrisonAug 27, 2025
    How to resolve dynamic braking fault in Lenze DC Drives?
    • M
      Matthew CookAug 27, 2025
      A dynamic braking fault in Lenze DC Drives typically means that the dynamic braking resistors are overheating. To resolve this, increase the deceleration time.
  • E
    Elizabeth LoganAug 27, 2025
    What to do if Lenze DC Drives have a single phase fault?
    • T
      timothychangAug 27, 2025
      If Lenze DC Drives have a single phase fault, it means a mains phase has been lost. Check the mains voltage.
  • J
    Jason ZimmermanAug 28, 2025
    What to do if Lenze DC Drives have a communication error?
    • K
      Kevin RosarioAug 28, 2025
      If Lenze DC Drives have a communication error, it may be because the serial timer has timed out. Check the serial link connections.
  • C
    cbrownAug 28, 2025
    What to do if Lenze Inverter shows short-circuit or overload?
    • C
      campbelldonaldAug 29, 2025
      If the Lenze Inverter experiences a short-circuit or overload, there are several potential causes: * A short-circuit itself: Investigate the cause and inspect the motor cable. * Excessive capacitive charging current: Use shorter motor cables. * Acceleration time is too short: Increase the acceleration time and check the controller selection. * Defective motor cable: Check the wiring. * Internal fault in the motor: Check the motor. * Frequent and long overload: Check controller selection.
  • K
    Kenneth George DVMAug 29, 2025
    Why is my Lenze ESMD112L4TXA Inverter showing overvoltage on DC bus?
    • L
      Lisa ByrdAug 29, 2025
      If your Lenze Inverter is experiencing an overvoltage on the DC bus, it could be due to several reasons: * The mains voltage might be too high: Verify the mains voltage. * The deceleration time might be excessively short, or the motor might be in generator mode: Increase the deceleration time or consider using a dynamic braking option. * Earth leakage on the motor side: Check the motor and motor cable, separating the motor from the controller to diagnose.
  • A
    Anthony SmithAug 30, 2025
    What causes motor overload on Lenze ESMD112L4TXA?
    • C
      Cynthia SmithAug 30, 2025
      If the Lenze Inverter displays a motor overload (I2t overload), it means the motor is thermally overloaded. This can be due to: * Impermissible continuous current. * Frequent or excessively long acceleration processes. To resolve this: * Check the controller selection. * Check the setting of c20.

Summary

Safety Information

General Safety, Application, and Installation

Covers general safety, application directives, installation, and electrical connection precautions.

UL System Warnings and Precautions

Specific warnings related to UL approved systems and critical hazard alerts.

Installation

Commissioning

Parameter Menu

Comprehensive list and explanation of all available drive parameters.

Troubleshooting & Fault Elimination

Status Codes and Basic Troubleshooting

Explanation of status codes and initial troubleshooting steps for operational issues.

Error Codes and Remedies

Detailed explanations of error codes and their corresponding corrective actions.

Specific Error Codes and Solutions

Troubleshooting for common errors like short-circuit, earth fault, overload, and overvoltage.

Lenze ESMD112L4TXA Specifications

General IconGeneral
Input Frequency50/60 Hz
Rated Power11 kW
Power Rating11 kW
Rated Current24 A
Output Current24 A
Protection ClassIP20
TypeInverter
Input Voltage380-480 V
Output Voltage0-480 V
Control MethodVector control
Cooling MethodVentilation