How to fix communication error on Lenze ESMD152L4TXA Inverter?
- PPatricia AustinSep 1, 2025
If the Lenze Inverter reports a communication error, it could be due to the serial timer timing out. In this case, check the serial link connections.

How to fix communication error on Lenze ESMD152L4TXA Inverter?
If the Lenze Inverter reports a communication error, it could be due to the serial timer timing out. In this case, check the serial link connections.
How to troubleshoot Remote keypad fault on Lenze Inverter?
If the Lenze Inverter shows 'Remote keypad fault', it means the remote keypad is disconnected. To resolve this, check the remote keypad connections.
What causes motor overload on Lenze Inverter?
If the Lenze Inverter displays a motor overload (I2t overload), it means the motor is thermally overloaded. This can be due to: * Impermissible continuous current. * Frequent or excessively long acceleration processes. To resolve this: * Check the controller selection. * Check the setting of c20.
What does it mean when Lenze DC Drives reach the current limit?
Reaching the current limit in Lenze DC Drives indicates a controllable overload, which is managed automatically.
What causes overvoltage on DC bus in Lenze DC Drives and how to fix it?
Overvoltage on the DC bus in Lenze DC Drives can be caused by several factors. It may be due to mains voltage being too high, so you should check the mains voltage. Another cause can be an excessively short deceleration time or the motor operating in generator mode; in this case, increase the deceleration time or use a dynamic braking option. Finally, earth leakage on the motor side can also cause this issue, so check the motor and motor cable, separating the motor from the controller.
What to do if Lenze DC Drives show data on EPM not valid?
If Lenze DC Drives indicate that the data on the EPM is not valid, it means the data is not valid for the controller. Use an EPM providing valid data or load the Lenze setting.
What causes automatic start to be inhibited in Lenze DC Drives?
If automatic start is inhibited in Lenze DC Drives, it is because c42 = 0. You should apply a LOW-HIGH signal change at terminal 28.
How to resolve dynamic braking fault in Lenze DC Drives?
A dynamic braking fault in Lenze DC Drives typically means that the dynamic braking resistors are overheating. To resolve this, increase the deceleration time.
What to do if Lenze DC Drives show undervoltage on DC bus?
If Lenze DC Drives show undervoltage on the DC bus, it could be because the mains voltage is too low. Check the mains voltage.
What to do if Lenze DC Drives have controller overtemperature?
If the controller has an overtemperature, it means the controller is too hot inside. To resolve this, reduce the controller load and improve cooling.
Explains symbols and their meanings for warnings and notes in the manual.
Details conformity standards, approvals, and environmental conditions for the inverter.
Provides power, voltage, current, and frequency ratings for various inverter models.
Covers dimensions, mounting details, and torque specifications for inverter installation.
Provides detailed dimensions and mounting instructions for the inverter unit.
Details electrical connection requirements, including EMC and wiring.
Guidelines for installing the inverter to meet Electromagnetic Compatibility (EMC) standards.
Recommendations for appropriate fuses, circuit breakers, and cable sizes for power wiring.
Illustrates the wiring connections for power, control, and communication terminals.
Details the function and connections for each control terminal on the inverter.
Guide to setting operational parameters and configuring the inverter's functions.
Information about the EPM for storing and managing controller memory and settings.
Detailed list and explanation of available parameters for configuring the inverter.
Lists common operational statuses, their causes, and recommended remedies.
Details specific error codes, their causes, and corrective actions.