How to fix communication error on Lenze Inverter?
- SShannon KelleySep 1, 2025
If the Lenze Inverter reports a communication error, it could be due to the serial timer timing out. In this case, check the serial link connections.

How to fix communication error on Lenze Inverter?
If the Lenze Inverter reports a communication error, it could be due to the serial timer timing out. In this case, check the serial link connections.
How to troubleshoot Remote keypad fault on Lenze ESMD752L4TXA?
If the Lenze Inverter shows 'Remote keypad fault', it means the remote keypad is disconnected. To resolve this, check the remote keypad connections.
What causes motor overload on Lenze ESMD752L4TXA Inverter?
If the Lenze Inverter displays a motor overload (I2t overload), it means the motor is thermally overloaded. This can be due to: * Impermissible continuous current. * Frequent or excessively long acceleration processes. To resolve this: * Check the controller selection. * Check the setting of c20.
What does it mean when Lenze DC Drives reach the current limit?
Reaching the current limit in Lenze DC Drives indicates a controllable overload, which is managed automatically.
What causes overvoltage on DC bus in Lenze DC Drives and how to fix it?
Overvoltage on the DC bus in Lenze DC Drives can be caused by several factors. It may be due to mains voltage being too high, so you should check the mains voltage. Another cause can be an excessively short deceleration time or the motor operating in generator mode; in this case, increase the deceleration time or use a dynamic braking option. Finally, earth leakage on the motor side can also cause this issue, so check the motor and motor cable, separating the motor from the controller.
What to do if Lenze DC Drives show data on EPM not valid?
If Lenze DC Drives indicate that the data on the EPM is not valid, it means the data is not valid for the controller. Use an EPM providing valid data or load the Lenze setting.
What causes automatic start to be inhibited in Lenze DC Drives?
If automatic start is inhibited in Lenze DC Drives, it is because c42 = 0. You should apply a LOW-HIGH signal change at terminal 28.
How to resolve dynamic braking fault in Lenze DC Drives?
A dynamic braking fault in Lenze DC Drives typically means that the dynamic braking resistors are overheating. To resolve this, increase the deceleration time.
What to do if Lenze DC Drives show undervoltage on DC bus?
If Lenze DC Drives show undervoltage on the DC bus, it could be because the mains voltage is too low. Check the mains voltage.
What to do if Lenze DC Drives have controller overtemperature?
If the controller has an overtemperature, it means the controller is too hot inside. To resolve this, reduce the controller load and improve cooling.
| Power Rating | 0.75 kW |
|---|---|
| Protection Class | IP20 |
| Series | ESMD |
| Communication Interface | RS485 |
| Operating Temperature | -10 ... 55 °C |
| Storage Temperature | -25 ... 70 °C |
| Relative Humidity | 95% (non-condensing) |
Covers live components, heat, unauthorized operation, and personnel qualifications.
Specifies intended use, machine compliance, and installation handling safety.
Emphasizes national regulations and EMC installation notes for safe electrical connections.
Highlights dangers of electric shock from charged capacitors and fire risk from protective devices.
Covers EMC requirements, noise emission, and cable screening for electrical installation.
Visual guide for wiring connections and overview of terminal layout.
Lists parameters C00 (Password entry) and C01 (Setpoint source) with their settings and importance.
Details error codes cF, CF, FI, CFG, dF, EEr, EF, F2_FO, FC3, FC5, LE, JF and their specific causes and remedies.
Explains errors OC1 (Short-circuit/overload), OC2 (Earth fault), OC6 (Motor overload), and their troubleshooting.
Covers OH (Controller overtemperature), OU (Overvoltage), St (Auto-TRIP reset), Sd5 (4-20mA reference), and SF (Single phase fault).