Operating instructions i510 cabinet frequency inverter | 31
© 11/2021 · EN · www.Lenze.com
Display code Name
Possible settings/
Value ranges
Keypad code Information
P400.03 Quick stop Not connected [0]
Assignment of a trigger to the “Activate quick stop” function.
Trigger = TRUE: Activate quick stop. Quick stop ramp adjustable in P225.00.
Trigger = FALSE: Deactivate quick stop
P400.04 Error reset Digital input 2 [12]
Assignment of a trigger to the “Reset error” function.
Trigger = FALSE > TRUE (edge): Active error is reset (acknowledged) if the error condition is not active anymore and the
error is resettable.
Trigger = FALSE: No action.
P400.05 DC braking Not connected [0]
Assignment of a trigger to the “Activate DC braking” function.
Trigger = TRUE: Activate DC braking.
Trigger = FALSE: Deactivate DC braking.
P400.06 Start forward Not connected [0]
Assignment of a trigger to the “Start forward (CW)” function.
Trigger = FALSE > TRUE (edge): Let motor rotate forward.
Trigger = TRUE > FALSE (edge): No action.
Stop via P400.01 (default setting of digital input 1).
P400.07 Start reverse Not connected [0]
Assignment of a trigger to the “Start reverse (CCW)” function.
Trigger = FALSE > TRUE (edge): Let motor rotate backward.
Trigger = TRUE > FALSE (edge): No action.
Stop via P400.01 (default setting of digital input 1).
P400.08 Run forward Not connected [0]
Assignment of a trigger to the “Run forward (CW)” function.
Trigger = TRUE: Let motor rotate forward.
Trigger = FALSE: Stop motor.
Stop via P400.01 (default setting of digital input 1).
P400.09 Run reverse Not connected [0]
Assignment of a trigger to the “Run reverse (CCW)” function.
Trigger = TRUE: Let motor rotate backward.
Trigger = FALSE: Stop motor.
Stop via P400.01 (default setting of digital input 1).
P400.13 Reverse rot. dir. Digital input 3 [13]
Assignment of a trigger to the “Reverse rotating direction” function.
Trigger = TRUE: The setpoint specied is inverted (i.e. the sign is inverted).
Trigger = FALSE: No action/deactivate function again.
P400.18 Setp: Preset B0 Digital input 4 [14]
Assignment of a trigger to the “Activate preset (bit 0)” function.
Bit with the valency 2
0
for the bit-coded selection and activation of a parameterized setpoint (preset value).
Trigger = FALSE: Bit = “0”.
Trigger = TRUE: Bit = “1”.
P400.19 Setp: Preset B1 Digital input5 [15]
Assignment of a trigger to the “Activate preset (bit 1)” function.
Bit with the valency 2
1
for the bit-coded selection and activation of a parameterized setpoint (preset value).
Trigger = FALSE: Bit = “0”.
Trigger = TRUE: Bit = “1”.
* Default setting dependent on the model