Error code Description Classication Remedy Blocking time [s]
2250 CiA: Continuous overcurrent (inside the device) Trouble
Check motor and wiring for short circuits.
Check brake resistor and wiring.
Check motor circuit (delta connection, star connection).
Check setting of the motor data.
5
2320 Short circuit or earth leakage on the motor side Trouble
Check motor cable.
Check the length of the motor cable.
Use shorter or lower-capacitance motor cable.
5
2340 CiA: Short circuit (inside the device) Trouble Check motor cable for short circuit. 5
2350 CiA: i²*t overload (thermal state) Trouble
Check drive sizing.
Check machine/driven mechanics for excessive load.
Check setting of the motor data.
Reduce values for slip compensation (P315.01, P315.02) and oscillation damping (P318.01, P318.02).
5
2382 Error: Device utilization (Ixt) too high Trouble
Check drive sizing.
Reduce maximum overload current of the inverter (P324.00).
In case of high mass inertias, reduce maximum overload current of the inverter (P324.00) to 150%.
3
2383 Warning: Device utilization (Ixt) too high Warning Check drive sizing. 0
3120 Mains phase fault Trouble
Check mains connection wiring.
Check fuses.
0
3210 DC bus overvoltage Trouble
Reduce dynamic performance of the load prole.
Check mains voltage.
Check settings for the brake energy management.
0
3211 Warning: DC bus overvoltage Warning 0
3220 DC bus undervoltage Trouble
Check mains voltage.
Check fuses.
Check DC bus voltage (P105.00).
Check mains settings.
0
3221 Warning: DC bus undervoltage Warning 0
3222 DC-bus voltage too low for switch-on Warning
Check mains voltage.
Check fuses.
Check mains settings.
0
4210 PU: Overtemperature fault Trouble
Check mains voltage.
Provide for a sucient cooling of the device (display of the heatsink temperature in P117.01).
Clean fan and ventilation slots. If required, replace fan.
Reduce switching frequency (P305.00).
0
4281 Heatsink fan warning Warning
Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can
then be removed.
0
5112 24 V supply critical Warning Check mains voltage. 0
5180 24-V supply overload Warning Check 24 V output and digital outputs for earth fault or overload. 0
6280 Trigger/functions connected incorrectly Trouble
Check and correct the assignment of the triggers to the functions.
With keypad or network control, the two functions “Inverter enable” (P400.01) and “Run” (P400.02) can also
be set to “Constant TRUE [1]” to start the motor.
0