Operating instructions i510 cabinet frequency inverter | 39
© 11/2021 · EN · www.Lenze.com
Error code Description Classication Remedy Blocking time [s]
7180 Motor overcurrent Trouble
• Check motor load.
• Check drive sizing.
• Adapt the set error threshold (P353.01).
1
9080 Keypad removed Trouble • Connect the keypad again or activate another control source. 0
FF06 Motor overspeed Trouble • Adapt the maximum motor speed (P322.00) and the error threshold (P350.01). 1
FF37 Automatic start disabled Trouble • Deactivate start command and reset error. 0
FF85 Keypad full control active Warning • Press the CTRL key to exit control mode. 0
Error codes
Troubleshooting
Error codes
LED statusError message