Parameter Name / value range / [default seng] Info
0x402E:003
(P822.03)
End segment: Time
(End segment: Time)
0.0 ... [0.0] ... 100000.0 s
From version 03.00
Delay me for acvang the output states congured for the end seg-
ment.
This parameter has a dierent meaning than the me sengs for the
segments 1 ... 8!
The set deceleraon me starts when the end segment is started to
be processed.
Aer the deceleraon me has elapsed:
The digital output is set to the level set in 0x402E:004 (P822.04) (if
congured accordingly).
The analog output is set to the voltage value set in 0x402E:005
(P822.05) (if congured accordingly).
The NetWordOUT2 data word is set to the value set in 0x402E:008.
0x402E:004
(P822.04)
End segment: Digital outputs
(End segment: Digital outp.)
0 ... [0] ... 255
From version 03.00
Oponally: Set digital outputs to the levels set here aer the me set for
the end segment.
Bit 0 Relay 0 = X9/NO-COM open and NC-COM closed.
1 = X9/NO-COM closed and NC-COM open.
An inversion set in 0x2635:001 (P421.01)is taken into consideraon
here.
Bit 1 Digital output 1 0 = set digital output 1 to LOW level.
1 = set digital output 1 to HIGH level.
An inversion set in 0x2635:002 (P421.02) is taken into consideraon
here.
0x402E:005
(P822.05)
End segment: Analog outputs
(End segment: Analog outp.)
0.00 ... [0.00] ... 10.00 VDC
From version 03.00
Oponally: Set analog output to the voltage value set here aer the me
set for the end segment.
Note!
In order that the control of the analog output is executed by the
sequencer, the following assignment must be made for the analog out-
put:
Analog output 1: 0x2639:002 (P440.02) = "Sequencer controlled [10]"
0x402E:006
(P822.06)
End segment: PID setpoint
(End segment: PID setp.)
-300.00 ... [0.00] ... 300.00 PID unit
From version 03.00
PID control value aer the sequence has been completed, i. e., aer the
steps congured for the sequence have been passed through with the
set numbers of cycles.
Only relevant if PID control is acvated in 0x4020:001 (P600.01) and
end of sequence mode 0x402F (P824.00) = "Keep running [0]".
0x402E:007
(P822.07)
End segment: Torque setpoint
(End segment: Torque setp.)
-400.0 ... [100.0] ... 400.0 %
From version 03.00
Torque setpoint aer the sequence has been completed, i. e., aer the
steps congured for the sequence have been passed through with the
set numbers of cycles.
Only relevant for the operang mode 0x6060 (P301.00) = "MS: Torque
mode [-1]" and if end of sequence mode 0x402F (P824.00) = "Keep
running [0]".
0x402E:008 End segment: NetWordOUT2
0 ... [0] ... 65535
From version 03.00
Oponally: Set NetWordOUT2 data word to the value set here aer the
me set for the end segment.
The NetWordOUT2 data word 0x400A:002 (P591.02) can be mapped
to a network register to transfer the set value as process date.
0x402E:009 End segment: Reserved
0 ... [0] ... 4294967295
From version 03.00
Sequencer
Segment conguraon
336

Table of Contents

Other manuals for Lenze I51AE175F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I51AE175F and is the answer not in the manual?

Lenze I51AE175F Specifications

General IconGeneral
BrandLenze
ModelI51AE175F
CategoryInverter
LanguageEnglish

Related product manuals