Parameter Name / value range / [default seng] Info
0x402E:003
(P822.03)
End segment: Time
(End segment: Time)
0.0 ... [0.0] ... 100000.0 s
•
From version 03.00
Delay me for acvang the output states congured for the end seg-
ment.
•
This parameter has a dierent meaning than the me sengs for the
segments 1 ... 8!
•
The set deceleraon me starts when the end segment is started to
be processed.
Aer the deceleraon me has elapsed:
•
The digital output is set to the level set in 0x402E:004 (P822.04) (if
congured accordingly).
•
The analog output is set to the voltage value set in 0x402E:005
(P822.05) (if congured accordingly).
•
The NetWordOUT2 data word is set to the value set in 0x402E:008.
0x402E:004
(P822.04)
End segment: Digital outputs
(End segment: Digital outp.)
0 ... [0] ... 255
•
From version 03.00
Oponally: Set digital outputs to the levels set here aer the me set for
the end segment.
Bit 0 Relay 0 = X9/NO-COM open and NC-COM closed.
1 = X9/NO-COM closed and NC-COM open.
An inversion set in 0x2635:001 (P421.01)is taken into consideraon
here.
Bit 1 Digital output 1 0 = set digital output 1 to LOW level.
1 = set digital output 1 to HIGH level.
An inversion set in 0x2635:002 (P421.02) is taken into consideraon
here.
0x402E:005
(P822.05)
End segment: Analog outputs
(End segment: Analog outp.)
0.00 ... [0.00] ... 10.00 VDC
•
From version 03.00
Oponally: Set analog output to the voltage value set here aer the me
set for the end segment.
Note!
In order that the control of the analog output is executed by the
sequencer, the following assignment must be made for the analog out-
put:
•
Analog output 1: 0x2639:002 (P440.02) = "Sequencer controlled [10]"
0x402E:006
(P822.06)
End segment: PID setpoint
(End segment: PID setp.)
-300.00 ... [0.00] ... 300.00 PID unit
•
From version 03.00
PID control value aer the sequence has been completed, i. e., aer the
steps congured for the sequence have been passed through with the
set numbers of cycles.
•
Only relevant if PID control is acvated in 0x4020:001 (P600.01) and
end of sequence mode 0x402F (P824.00) = "Keep running [0]".
0x402E:007
(P822.07)
End segment: Torque setpoint
(End segment: Torque setp.)
-400.0 ... [100.0] ... 400.0 %
•
From version 03.00
Torque setpoint aer the sequence has been completed, i. e., aer the
steps congured for the sequence have been passed through with the
set numbers of cycles.
•
Only relevant for the operang mode 0x6060 (P301.00) = "MS: Torque
mode [-1]" and if end of sequence mode 0x402F (P824.00) = "Keep
running [0]".
0x402E:008 End segment: NetWordOUT2
0 ... [0] ... 65535
•
From version 03.00
Oponally: Set NetWordOUT2 data word to the value set here aer the
me set for the end segment.
•
The NetWordOUT2 data word 0x400A:002 (P591.02) can be mapped
to a network register to transfer the set value as process date.
0x402E:009 End segment: Reserved
0 ... [0] ... 4294967295
•
From version 03.00
Sequencer
Segment conguraon
336