Parameter Name / value range / [default seng] Info
0x2824
(P200.00)
Control selecon
(Control select.)
Selecon of the type of inverter control.
0 Flexible I/O conguraon This selecon enables a exible assignment of the start, stop, and rotat-
ing direcon commands with digital signal sources.
•
Digital signal sources can be digital inputs, network and keypad.
•
The I/O conguraon is made via the parameters 0x2631:xx (P400.xx).
1 Keypad This selecon enables the motor to be started exclusively via the start
key of the keypad. Other signal sources for starng the motor are
ignored.
Start motor Stop motor
Note!
•
The funcons "Enable inverter" 0x2631:001 (P400.01) and "Run"
0x2631:002 (P400.02) must be set to TRUE to start the motor.
•
If jog operaon is acve, the motor cannot be stopped via the
keypad key.
Flexible I/O conguraon
Control source change-over
347