EasyManuals Logo

Lenze I55BE F Series User Manual

Lenze I55BE F Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
Electrical installaon
Operang Instrucons i550-Cabinet
5.7 1-phasemainsconnecon230/240V
Terminaldata,1-phase230/240V
I55AxxxB I55AxxxA I55AxxxA I55AxxxA
Inverter [kW] 0.25 ... 0.75 1.1 ... 2.2 0.25 ... 2.2 0.25 ... 2.2
Connecon Mains connecon X100 PE connecon
Motor
connecon X105
Connecon type Pluggable screw terminal PE screw Pluggable screw
terminal
Min. cable cross-secon mm² - - -
Max. cable cross-secon mm² 2.5 6 6 2.5
Stripping length mm 8 10 8
Tightening torque Nm 0.5 0.7 2 0.5
Tools required 0.5 x 3.0 0.6 x 3.5 Torx 20 0.5 x 3.0
Fusing data
Inverter [kW] 0.25 0.37 0.55 0.75 1.1 1.5 2.2
Rated output current (8 kHz) A 1.7 2.4 3.2 4.2 6 7 9.6
Max. output current (15 s) A 2.6 3.6 4.8 6.3 9 10.5 14.4
Operaonwithoutmainschoke
Rated mains current A 4 5.7 7.6 10 14.3 16.7 22.5
Fuse
Characterisc gG/gL or gRL
Max. rated current A 10 10 16 16 25 25 25
Circuit breaker
Characterisc B
Max. rated current A 10 10 16 16 25 25 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type B
Mainsconnecon
1/N/PE
AC 170 V ... 264 V
45 Hz ... 65 Hz
F1
Q1
X100
L1
L2/N
PE
N
L3
L2
3/N/PE
AC 400 V
L3
2/PE
AC 170 V ... 264 V
45 Hz ... 65 Hz
F1
F2
Q1
X100
L1
L2/N
PE
N
L3
L2
3/N/PE
AC 208 V ... 240 V
L3
F1
F2
Q1
X100
L1
L2/N
2/PE
AC 170 V ... 264 V
45 Hz ... 65 Hz
PE
N
L2
2/N/PE
AC 208 V ... 240 V
Motorconnecon
X105
U
V
W
Rb1
Rb2
M
3~