EasyManuals Logo

Lenze I55BE F Series User Manual

Lenze I55BE F Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
5
Safety instrucons
Operang Instrucons i550-Cabinet
1.5 Idencaonoftheproducts
I 5 5 A E xxx x 1 x x x x xxxx
Product type Inverter I
Product family i500 5
Product i550 5
Product generaon Generaon 1 A
Mounng type Control cabinet mounng E
Rated power [hp]
(examples)
0.33 hp 125
10 hp 275
125 hp 390
150 hp 411
Mains voltage and
connecon type
(examples)
1/N/PE AC 120 V A
3/PE AC 230/240 V B
Motor connecons Single axis 1
Integrated funconal
safety
Without safety funcon 0
Basic Safety STO A
Degree of protecon IP20, coated V
Interference suppres-
sion
Without 0
Integrated RFI lter 1
Applicaon Default parameter seng: Region
US (60-Hz networks)
1
Design types
(examples)
Standard I/O without network 000S
Applicaon I/O without network 001S
2 Safetyinstrucons
2.1 Basic safety measures
Disregarding the following basic safety measures may lead to severe personal injury and
damage to property!
The product:
must only be used as directed.
must never be commissioned if they display signs of damage.
must never be technically modied.
must never be commissioned if they are not fully mounted.
must never be operated without required covers.
must only be disconnected from the installaon in de-energized condion.
Connect/disconnect all pluggable terminals only in de-energized condion.
Carry out insulaon resistance tests between 24-V control potenal terminals and PE.
The maximum test voltage must not exceed 110 V DC.
The safety measures are the condion for safe and trouble-free operaon and the achieve-
ment of the specied product features.
The procedural notes and circuit details given in this document are suggesons and their
transferability to the respecve applicaon has to be checked. The manufacturer does not
take responsibility for the suitability of the process and circuit proposals.
The product may cause EMC interferences. The operator is responsible for execung the
interference suppression measures.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze I55BE F Series and is the answer not in the manual?

Lenze I55BE F Series Specifications

General IconGeneral
BrandLenze
ModelI55BE F Series
CategoryInverter
LanguageEnglish

Related product manuals