17
Electrical installaon
Operang Instrucons i550-Cabinet
Terminaldata,3-phase480V
I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF I55AxxxF
Inverter [kW] 30 ... 45 55 ... 75 90 ... 132 30 ... 75 90 ... 132 30 ... 45 55 ... 75 90 ... 132
Connecon Mains connecon X100 PE connecon Motor connecon X105
Connecon type Screw terminal PE screw PE bolt Screw terminal
Min. cable cross-secon mm² 1 1.5 1
Max. cable cross-secon mm² 50 95 150 25 150 50 95 150
Stripping length mm 19 22 28 16 - 19 22 28
Tightening torque Nm 4 10 18 4 10 4 10 18
Tools required Hexagon socket
5
Hexagon socket
6
Hexagon socket
8
PZ2 Wrench size 13 Hexagon socket
5
Hexagon socket
6
Hexagon socket
8
Fusing data
Inverter [kW] 30 37 45 55 75 90 110 132
Rated output current (8 kHz)
(Heavy Duty)
A 52 65 77 96 124 156 180 -
Max. output current (15 s) A 78 98 116 144 186 234 270 -
Rated output current
(Light Duty)
A 48.5 62.4 78 92.4 115 149 187 216
Max. output current (15 s) A 61 78 98 116 144 186 234 270
Operaonwithmainschoke
Rated mains current A 45.7 57 66.7 83 113 146 168 -
Fuse
Characterisc gG/gL or gRL gR
Max. rated current A 80 100 125 160 160 300 300 300
Circuit breaker
Characterisc B
Max. rated current A 80 100 125 - - - - -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
In case of Light Duty above 15 kW and Heavy Duty above 30 kW, a mains choke must be used.
Mainsconnecon
+UG
3/PE
AC 340 V ... 528 V
45 Hz ... 65 Hz
F1
…
F3
Q1
X100
L1
L2
L3
PE
N
L3
L2
3/N/PE
AC 480 V
-UG
Motorconnecon
X105
U
V
W
Rb1
Rb2
M
3~