22
Commissioning
Operang Instrucons i550-Cabinet
Display code Designaon Possiblesengs/valueranges Keypad code Informaon
P203.03 Stop method Coasng [0] The motor has no torque (coasts down to standsll).
Standard ramp [1] The motor is brought to a standsll with the deceleraon me 1 P221.00 (or deceleraon me 2 P223.00 if acvated).
Quick stop ramp [2] The motor is brought to a standsll with the deceleraon me (P225.00) set for the "quick stop" funcon.
Switch-o posioning [3] Is similar to the stop method “standard ramp [1]“. Depending on the actual output frequency, however, the inverter delays the beginning of the
down-ramping so that the number of motor revoluons unl a standsll is reached and thus the stopping posion is always relavely constant.
P208.01 Mains voltage 230Ve [0] Selecon of the mains voltage for actuang the inverter.
400 Ve [1]
480 Ve [2]
120 Ve [3]
P210.00 Min. frequency 0.0 ... 599.0 Hz Lower limit value for all frequency setpoints.
P211.00 Max. frequency Device for 50-Hz mains: 50
Hz * Device for 60-Hz mains:
60 Hz *
Upper limit value for all frequency setpoints.
P220.00 Acceleraon 1 0.0 ... 5.0 ... 3600.0 s Acceleraon me 1.
P221.00 Deceleraon 1 0.0 ... 5.0 ... 3600.0 s Deceleraon me 1
P300.00 Motor ctrl mode Servo control (SC ASM) [2] This control mode is used for servo control of an asynchronous motor. This motor control mode is described in the commissioning manual.
hp://www.Lenze.com
Sensorless control (SL PSM) [3] This control type is used for the sensorless control of a synchronous motor. This motor control mode is described in the commissioning manual.
hp://www.Lenze.com
Sensorless vector control
(SLVC)
[4] This control type is used for sensorless vector control of an asynchronous motor. For this purpose, observe the parameters P327.04 and
P327.05 for idenfying and calibrang the motor.
VFCopenloop [6] This control mode is used for the speed control of an asynchronous motor via a V/f characterisc and is the simplest control mode.
V/f characterisc control
(VFC closed loop)
[7] The control mode is used for speed control of an asynchronous motor via a V/f characterisc with speed feedback.
This motor control mode is described in the commissioning manual. hp://www.Lenze.com
P302.00 V/f characterisc
shape
Linear [0] Linear characterisc for drives with constant load torque over the speed.
Square-law [1] Square-law characterisc for drives with a square-law load torque over the speed.
Eco [3] Linear characterisc with energy opmizaon in the paral load operaonal range.
P303.01 Base voltage 0 ... 230 ... 5000 V * Base voltage and base frequency dene the V/f rao and thus the gradient of the V/f characterisc.
The V/f base voltage is usually set to the rated motor voltage.
The V/f base frequency is usually set to the rated motor frequency.
P303.02 Base frequency Device for 50-Hz mains:
50 Hz *
Device for 60-Hz mains:
60 Hz *
Base voltage and base frequency dene the V/f rao and thus the gradient of the V/f characterisc.
The V/f base voltage is usually set to the rated motor voltage.
The V/f base frequency is usually set to the rated motor frequency.
P304.00 Limitaon of rotaon Only clockwise (CW) [0] The motor can only be rotated clockwise (CW). The transfer of negave frequency and PID setpoints to the motor control is prevented.
Bothrotaondirecons [1] Both direcons of motor rotaon are enabled.
P305.00 Switching frequency 8 kHz var/opt/4 * Selecon of the inverter switching frequency.
P306.01 Overload selecon Heavy duty [0] Load characterisc for high dynamic requirements.
Light duty [1] Load characterisc for low dynamic requirements.
P308.01 Max. load for 60s 30 ... 150 ... 200 % Maximum permissible thermal motor ulizaon (max. permissible motor current for 60 seconds). With regard to rated motor current (P323.00)
P316.01 Fixed V/f boost 0.0 ... 2.5 ...20.0 % * Constant voltage boost for the V/f characterisc control without feedback.