SM100_SS1_SMX_11_PL_e_en.pdf
9400 with SM100
Safe stop 1 with BBH SMX 11
(architecture according to performance level e of EN ISO 13849-1)
Connection diagram (section):
When the safety function is requested, the motor is stopped according to stop category 1 of EN
60204-1.
The delay time in the SMX 11 must be longer than the QSP time. The values to be set depend on the
application.
Since the SM100 does not contribute to the probability of failure on demand (PFD) and to the
probability of failure per hour (PFH), the feedback DO1 need not be used. All safety-relevant errors
that can occur in the SM100 result in the safe state. Faults have been excluded for protected cables
(according to DIN EN ISO 13849-2:2008-09 and DIN EN 61800-5-2:2008-04). This applies to
cables which are protected by a cable duct and installed inside the control cabinet.