44
WARNINGS:
• HAZARD OF ELECTROCUTION, SHOCK, EXPLOSION, OR ARC FLASH.
CAREFULLY READ AND FOLLOW INSTRUCTIONS.
• TO AVOID FIRE, SHOCK OR DEATH, turn OFF all power supplying equipment before
working on or inside the equipment. Use a properly rated voltage sensing device to
conrm power is OFF.
•
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment MUST be installed and serviced by an electrician or other qualied
personnel with the requisite knowledge, training and experience related to the
installation and operation of this equipment.
• Product may use multiple voltage/power sources. Be sure all sources of power have
been disconnected before servicing.
• Do not depend on this product for voltage indication.
• Only install this product on insulated conductors.
• If the meter appears damaged or defective, rst disconnect all power to the meter. Then
call or e-mail technical support for assistance.
DO NOT EXCEED 346V Line to Neutral (L-N) or 600V Line to Line (L-L). This meter is
equipped to monitor loads up to 346V L-N. Exceeding this voltage will cause damage to
the meter and danger to the user. Always use a Potential Transformer (PT) for voltages in
excess of 346V L-N or 600 volts L-L. VerifEye
®
branded meters are 600 Volt Over Voltage
Category III devices.
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2
environment must control conductive pollution and the possibility of condensation or
high-humidity. Consider the enclosure, the correct use of ventilation, thermal properties
of the equipment, and the relationship with the environment.
Installation category: CAT II or CAT III.
Provide a disconnect device to disconnect the meter from the supply source. Place
this device in close proximity to the equipment, within easy reach of the operator, and
mark it as the disconnecting device. The disconnecting device must meet the relevant
requirements of IEC 60947-1 and IEC 60947-3, and be suitable for the application. In the
US and Canada, disconnecting fuse holders can be used. Provide over-current protection
and disconnecting device for supply conductors with approved current-limiting devices
suitable for protecting the wiring. If the equipment is used in a manner not specied by
the manufacturer, the protection provided by the device may be impaired.
1 WARNINGS AND CAUTIONS