Installation
12
Installation Space
1) Indoor Unit
• The following values are the least space for installation. If any service area is needed for service
according to field circumstance, obtain enough service space.
• The unit of values is mm.
(Unit: mm)
400520300
Service space
(front side)
330
600
Piping space
(front side)
Service space
(left side)
100100100100
200
10801080
H-Beam supporter
space
(Unit: mm)
Air inlet grille
500
Strong
wind
Strong
wind
Blown
air
3. When installing the outdoor unit in a place that is constantly exposed to a strong wind like a coast
or on a high story of a building, secure a normal fan operation by using a duct or a wind shield.
• Install the unit so that its discharge port faces to the wall of the building.
Keep a distance 500mm or more between the unit and the wall surface.
• Supposing the wind direction during the operation season of the air conditioner, install the unit
so that the discharge port is set at right angle to the wind direction.