EasyManua.ls Logo

LG ARNU243SCL4 - Art Cool Mirror Electrical Data

LG ARNU243SCL4
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22 | ART COOL
TM
MULTI V Wall-Mounted Indoor Unit Engineering Manual
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©
/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
Electrical Data
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of a fuse, use the circuit breaker.
Model Number
Voltage
Range
MCA MOP Rated Amps (A)
Power Supply Power Input (W)
Hz Volts Phase Cooling Heating
6%)UDPHV
ARNU053SBR4
187-253
0.2
15
0.16
60 208-230V 1
21 21
ARNU073SBR4 0.2 0.16 21 21
ARNU093SBR4 0.2 0.16 21 21
ARNU123SBR4 0.2 0.16 21 21
ARNU153SBR4 0.2 0.16 21 21
6&)UDPHV
ARNU183SCR4
187-253
0.36
15
0.29
60 208-230V 1
39.5 39.5
ARNU243SCR4 0.36 0.29 39.5 39.5
Table 11: Art Cool Mirror Wall-Mounted Indoor Unit Electrical Data.
ART COOL
TM
MIRROR