31
ENGLISH
FUNCTIONAL SPECIFICATIONS AC Smart BACnet
Point
No.
Control/monitoring
Object Name
(XXX : ventilation
address)
Object
Type
Unit
Inactive Active
Text- 0 Text-1 Text-2 Text-3 Text- 4 Text- 5
16 Error Code MalfunctionCode_XXX AI Reference LG Original Error Code
17 User Mode(Setting)
UserModeCommand_
XXX
MO
Quick
Fresh
Energy
Saving
Heater
18 User Mode(Status) UserModeStatus_XXX MI
Quick
Fresh
Energy
Saving
Heater
19 °C
20 - - -
21
AC Operation Mode
(setting)
HrvModeCommand_XXX MO Cool Auto Heat
22
AC Operation Mode
(status)
HrvModeStatus_XXX MI Cool Auto Heat
23 AC ON/OFF (setting)
HrvStartStopCommand_
XXX
BO Stop Run
24 AC ON/OFF (status) HrvStartStopStatus_XXX BI Stop Run
25 AC Humidify (setting)
HrvHumidifyCommand_
XXX
BO Off On
26 AC Humidify (status) HrvHumidifyStatus_XXX BI Off On