41
ENGLISH
FUNCTIONAL SPECIFICATIONS AC Smart BACnet
BACnet Point List : GENERAL
AC Smart BACnet has a GENERAL Point List as follows.
Some of GENERAL Points may not be supported depending on the product.
The product should be rebooted when temperature unit setting is modified.
Point
No.
Control/monitoring
Object Name
(XXX : Unit address)
Object
Type
Unit
Inactive Active
Text- 0 Text-1 Text-2 Tex t- 3 Text- 4 Text- 5
1
All Unit Run/Stop (Setting)
AllStartStopCommand
BO
Stop Run
2
All Unit Set Room Temperature
(Setting)
AllSetRoomTempCommand
AV °C
3
All Unit Temperature Lock
(Setting)
AllTempLockCommand
AV °C
4
Total Accumulated Power (Status)
TotalAccumulatedPower
AI
5
Peak Control Operation (Setting)
PeakStartStopCommand
BO Stop
Run
6
Peak Control Operation (Status)
PeakStartStopStatus
BI Stop
Run
7
Peak Shift Time(Setting)
PeakShiftTimeCommand
AV Minute
8
Peak Shift Time(Status)
PeakShiftTimeStatus
AI Minute
9
Peak Target Ratio(Setting)
PeakTargetCommand
AV %
10
Peak Target Ratio(Status)
PeakTargetStatus
AI %
11
Peak Current Running
Ratio(Status)
PeakCurrentStatus
AI %
12
Remote Shutdown(Setting)
RemoteShutDownCommand
BO Normal
Shutdown
13
Temperature Unit Setting
(Setting)
TempUnitCommand
BO °C ˚F
14
Temperature Unit Setting (Status)
TempUnitStatus
BI °C ˚F