- 34 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Part 2 Functions & Controls
ABNH36GGLA2
Setting Value
Static Pressure[mmAq(Pa)]
4(49) 6(59) 8(78) 10(98)
115 25.9 - - -
120 27.9 - - -
125 29.9 26.4 - -
130 32.0 28.5 25.0 -
135 - 30.7 27.5 -
140 - 32.9 29.9 26.0
145 - - 32.3 28.5
150 - - - 31.0
155 - - - -
(Unit: CMM)
ABNH48GRLA2
Setting Value
Static Pressure[mmAq(Pa)]
6(59) 8(78) 10(98) 12(118)
85 31.5 - - -
90 36.3 29.8 - -
95 41.3 34.5 28.4 -
100 45.4 39.7 33.5 27.3
105 - 44.1 38.6 33.1
110 - - 44.2 38.9
115 - - - 44.7
(Unit: CMM)
ABNH42GRLA2
Setting Value
Static Pressure[mmAq(Pa)]
6(59) 8(78) 10(98) 12(118)
85 31.5 - - -
90 36.3 29.8 - -
95 41.3 34.5 28.4 -
100 45.4 39.7 33.5 27.3
105 - 44.1 38.6 33.1
110 - - 44.2 38.9
115 - - - 44.7
(Unit: CMM)
ABNH60GRLA2
Setting Value
Static Pressure[mmAq(Pa)]
6(59) 8(78) 10(98) 12(118) 14(137)
95 41.3 - - - -
100 45.4 39.7 - - -
105 49.5 44.1 38.6 - -
110 - 48.5 44.2 38.9 -
115 - - 49.8 44.7 42.2
120 - - - 50.5 48.1
(Unit: CMM)