11
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
Table 2: Single Zone Extended Pipe Indoor Unit Electrical Data.
Electrical
Nominal
Tons
Unit Model
Number
Hertz Voltage
Voltage Range
(Min. to Max.)
MCA MOP
Compressor
Qty.
Compressor Motor
RLA
Outdoor Fan
Motor
Indoor Fan
Motor
Cooling Heating W FLA W FLA
2 LS243HLV3
60 208 - 230 187 - 253
19.0 30 1 14.41 14.41 124 0.4 58 0.5
2-1/2 LS303HLV3 23.0 30 1 15.1 15.1 124 0.25 110 0.5
2-3/4 LS363HLV3 23.0 30 1 15.1 15.1 124 0.25 110 0.5
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.