Service Manual 41
3-Way Valve
CLOSE
OPEN
Gas side
Liquid side
Indoor unit
Outdoor unit
Open
Open
3-Way
valve
3-Way
valve
2) Balance refrigerant of the 3-way(liquid side), 3-way(gas side) valves
(Gas leakage)
Procedure
Confirm that both the liquid side and gas side valves are set to the back seat.
Connect the charge set to the 3-way(gas side) valve's port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
Open the valve (Lo side) on the charge set and discharge the refrigerant until the gauge indicates 0 kg/cm
2
g.
- If there is no air in the refrigerant cycle (the pressure when the air conditioner is not running is higher than 1
kg/cm
2
g), discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm
2
g. In case of this, it will not be nec-
essary to apply an evacuation.
- Discharge the refrigerant gradually; if it is discharged too suddenly, the refrigeration oil will also be discharged.