36 Outdoor Unit
Refrigerant piping system
WARNING
When the equivalent length between a outdoor and the farthest indoor unit
is 90m(295ft) or more, main pipe(A) must be increased one grade.
Ú Refrigerant pipe diameter from outdoor unit to first branch. (A)
(**) Conditional Application(Incase of D12 is the farthest indoor)
Below condition must be satisfied for 40m(131ft) ~ 90m(295ft) piping length after first branch.
1) Diameter of pipes between first branch and the last branch should be increased by one step,
except if the pipe diameter B,C3 is same as Diameter A(Main pipe diameter)
Ø6.35(1/4) Ø 9.52(3/8) Ø 12.7(1/2) Ø 15.88(5/8) Ø 19.05(3/4) Ø 22.2(7/8) Ø 25.4*(1),
Ø 28.58(1-1/8) Ø 31.8*(1-1/4), Ø 34.9(1-3/8) Ø 38.1*(1-1/2)
* : If available on site, it use this size. Otherwise it can't be increased.
2) While calculating total refrigerant piping length, pipe B,C3 length should be calculated twice.
A + B x 2 + C3 x 2 + C1 + C2 + a + b + c + d + e + f + g + i + j + k + l + m + n ≤ 1,000m(3,280ft)
3) Length of pipe from each indoor unit to the closest HR Unit (a,b,c,d,e,e,g,i,j,k,l,m,n) ≤
40m(131ft)
4) [Length of pipe from outdoor unit to the farthest indoor unit D12 (B+C3+K)]
- [Length of pipe outdoor unit to the closest indoor unit D1 (C1+a)] ≤ 40m(131ft)
h If available on site, it use this size. Otherwise it can't be increased.
Upward outdoor
unit total capacity
Pipe diameter Pipe diameter when pipe length is 90m over to 1st branch
HP
Liquid
mm(inch)
Low pressure gas pipe
mm(inch)
High pressure gas pipe
mm(inch)
Liquid
mm(inch)
Low pressure gas pipe
mm(inch)
High pressure gas pipe
mm(inch)
8
9.52(3/8)
19.05(3/4) 15.88(5/8)
12.7(1/2)
22.2(7/8) 19.05(3/4)
10 22.2(7/8)
19.05(3/4)
25.4(1)
22.2(7/8)
12
12.7(1/2)
28.58(1-1/8)
15.88(5/8)
31.8(1-1/4)
14
22.2(7/8) 25.4(1)
16
18
15.88(5/8) 19.05(3/4)
20
22
34.9(1-3/8)
28.58(1-1/8)
38.1(1-1/2)
31.8(1-1/4)
24
26
19.05(3/4) 22.2(7/8)
28
30
32
34
36
41.3(1-5/8) 44.5(1-3/4)
38
40
42
34.9(1-3/8) 38.1(1-1/2)
44
46
48
50
52
54
56
58
60
62
22.2(7/8)
44.5(1-3/4) 41.3(1-5/8)
25.4(1) 53.98(2-1/8)
44.5(1-3/4)
64
66
53.98(2-1/8) 44.5(1-3/4) 53.98(2-1/8)
68
70
72
74
76
78
80

Other manuals for LG multi V ARUM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG multi V ARUM Series and is the answer not in the manual?

LG multi V ARUM Series Specifications

General IconGeneral
BrandLG
Modelmulti V ARUM Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals