EasyManua.ls Logo

LG Multi V ARUN053GF2 - Headers Installation and Fitting Table

LG Multi V ARUN053GF2
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34
MULTI V Space II Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
REFRIGERANT PIPING CONNECTIONS
Headers
The largest-capacity indoor unit must be installed closest to the Space II unit
Install the Header in a horizontal plane.
If the diameter of the refrigerant piping is different from the Header port size, trim to the desired section
using a pipe cutter.
When the number of pipes to be connected is less than the number of available header branches,
install a cap to the unused ports.
Headers should be insulated with the clam-shell jacket included in each kit.
Branch Pipe Fittings
Unit: inch
Models Vapor pipe Liquid pipe
4 branch
ARBL054
7 branch
ARBL057
4 branch
ARBL104
7 branch
ARBL107
10 branch
ARBL1010
10 branch
ARBL2010
14-3/16
21-1/4
21-1/4
4-3/4
I.D. 5/8
I.D. 1/2
I.D. 1/2
I.D. 5/8
I.D. 5/8
I.D. 3/4
4-3/4
14-3/16
I.D. 3/8
I.D. 3/8
I.D. 1/4
I.D. 1/4
I.D. 3/8
I.D. 1/2
5-15/16
5-15/16
5-15/16
15-3/4
6-5/16
I.D. 5/8
I.D. 1/2
I.D. 3/4
I.D. 5/8
I.D. 7/8
I.D. 1-1/8
I.D. 1
4-3/4
4-3/4
4-3/4
4-3/4
4-3/4
4-3/4
4-3/4
I.D. 5/8
I.D. 1/2
I.D. 5/8
I.D. 1/2
I.D. 5/8
I.D. 3/4
4-3/4
I.D. 1/4
I.D. 3/8
I.D. 3/8
I.D. 1/2
6-5/16
22-7/8
I.D. 3/4
I.D. 5/8
ID15.885/8
I.D. 5/8
I.D. 1/2
I.D. 7/8
I.D. 1-1/8
I.D. 1
27-/1 6
4-3/4
I.D. 1/4
I.D. 3/8
I.D. 3/8
I.D. 1/4
I.D. 3/8I.D. 1/2
I.D. 5/8
I.D. 1/2
4-3/4
28-3/8
I.D. 1/4
I.D. 3/8
I.D. 3/8
I.D. 1/4
I.D. 1/2
I.D. 3/8
4-1/4
21-1/2
27-/1 6
I.D. 1/4
I.D. 3/8
I.D. 3/4
I.D. 5/8
I.D. 3/8
I.D. 1/4
4-3/4
4-3/4
6-5/16
2-7/8
I.D. 3/4
I.D. 5/8
I.D. 7/8
I.D. 1-1/8
I.D. 1
7-3/16
3-/16
I.D. 3/4
I.D. 5/8
I.D. 5/8
I.D. 1/2
I.D. 1-1/8
I.D. 1-1/4
I.D. 1-3/8
5-15/16
5-15/16
5-15/16
4-3/4
4-3/4
14-3/16
I.D. 3/8
I.D. 3/8
I.D. 1/4
I.D. 1/4
I.D. 3/8
I.D. 1/2
5-15/16
5-15/16
4-3/4
5-15/16
4-3/4
5-15/16
5-15/16
4-3/4
5-15/16
A
B
Pipe Cutter
T
o
Space unit
T
o
indoor unit
A
B
Table 23: Header Table.
Capped Pipe
Horizontal Plane
Viewed from this point
in the direction of the arrow.
Figure 33: Header Installation.
Figure 34: Capping Unused Ports
and Horizontal Plane.

Related product manuals