Error Code Description Details
Space II Unit
8 6 1 Space II unit main PCB onboard EPROM error.
Verify the EPROM is present and in the socket correctly.
Check if all pins are in and are not bent.
Check if notch in the chip lines up with the arrow on the
socket.
8 7 1 Space II unit fan PCB EPROM error.
Communication error between Space II unit fan MICOM and
EPROM.
EPROM is missing.
8 8 1 PFC PCB EPROM Error
Communication error between Space II unit PFC MICOM and
EPROM.
EPROM is missing.
1 0 5 1 Space II unit fan PCB communication error. Space II unit main PCB is not receiving a signal from the fan.
1 0 6 1 Space II unit fan IPM error. Instant overcurrent (peak) of Space II unit fan IPM.
1 0 7 1 Space II unit fan DC link low voltage error. Space II unit fan DC link voltage is <140V (for 208-230V units).
1 1 3 1 Space II unit liquid pipe temperature sensor error.
Check the connection on the Space II unit PCB.
Thermistor has disconnected or short circuited.
1 1 4 1 Space II unit subcooling outlet temperature sensor error.
1 1 5 1 Space II unit subcooling inlet temperature sensor error.
1 5 1 1 Space II unit operation mode conversion error. Space II unit is experiencing a pressure imbalance.
1 8 2 1
Communication error between Space II unit external
board main and sub MICOMs.
Space II unit external board main to sub MICOMs communica-
tion failure.
1 9 1 1
Space II unit inverter PCB heatsink temperature sensor
error.
Space II unit inverter PCB heatsink temperature sensor has
disconnected or short circuited.
1 9 3 1 Space II unit fan PCB heatsink temperature error.
System has shut off because Space II unit fan PCB heatsink
temperature is >203°F.
1 9 4 1
Space II unit fan PCB heatsink temperature sensor
error.
Space II unit fan PCB heatsink temperature sensor has discon-
nected or short circuited.
Table 31: Error Codes, continued.