PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
35
ENGLISH
Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
22.4(76,400)
Ø9.52(3/8) Ø19.05(3/4)
< 36.4(124,200) Ø9.52(3/8) Ø22.2(7/8)
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
total capacity(HP)
Liquid pipe [mm(inch)] Gas pipe [mm(inch)]
8 Ø9.52(3/8) Ø19.05(3/4)
10 Ø9.52(3/8) Ø22.2(7/8)
12 Ø12.7(1/2) Ø28.58(11/8)