Installation Manual 27
Refrigerant piping installation
ENGLISH
◆ Indoor Unit Connection
◆ Distribution Method
Line Distribution
With line distribution method, it is possible to make the first or the second main pipe distribution within the
third branch, And do not make the main pipe distribution, at or after the fourth branch.
Note-
Main Pipe Distribution : Distribution from One Multi-kit to Two Multi-kits(mark with a circle)
➲ Indoor unit connecting pipe from branch (a,b,c,d,e)
Total pipe length ≤ 220m Total pipe length ≤ 100m
Downward indoor unit total capacity
[kW(Btu/h)]
2.1(7,000), 2.6(9,000), 3.5(12,000)
5.3(18,000), 7.0(24,000), 8.2(28,000)
10.5(36,000), 12.3(42,000), 14.0(48,000)
Ø6.35(1/4)
Ø9.52(3/8)
Ø9.52(3/8)
Ø12.7(1/2)
Ø15.88(3/8)
Ø19.05(3/4)
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]