EasyManua.ls Logo

LG MULTI V MINI ARUN047GS2 - How to Connect Central Controller

LG MULTI V MINI ARUN047GS2
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Wiring
ENGLISH
Installation Manual 51
u How to connect central controller (U3 Chassis, 2 Fan Model)
- The communication lines connected to INTERNET terminal should be connected to central control of Outdoor
unti with care for their polarity( A A, B B )
- Connect communication lines between outdoor unit and indoor units through the terminal block.
- When connecting communication line between outdoor unit and indoor units with shielded wire, connect the
shield ground to the earth screw.
- When connecting the central control system with shielded wire, connect the shield ground to the earth screw.
Terminal block on the main PCB
SODU IDU INTERNET DRY1 DRY2
B
A
B(D) A(C)
GND 12V
Outdoor Units

Table of Contents