88 Outdoor Unit
Test Run
Integrated Test Running Function_Cooling Mode (Setting 3)
This function is checking process for normal operation of parts and system On operating system.
• All processes carry out included refrigerant amount judge logic and check normal condition of parts on cool-
ing mode.
• This function check only normal condition of parts on heating mode.
• Saved data can check using LGMV.
Note
1. Judge the normal condition refer to report of Test Running.
Thermo off
IDU judge
Start
Temp. Condition
1 IDU operation
1 IDU operation data
(10min)
Refrigerant amount judge
during all IDU operation
data on Test Runing(15min)
Error Display
Error Display
Press the black button for 2 sec
Yes
No
Note 1
End
Press the black button for 2 sec.
after turning off all of Dip switch.
Completed
Yes
All IDU operation on
Cooling mode
Press the black button for 2 sec
DIP Switch Settings
Warning : Please reset Main PCB before starting this function

Other manuals for LG Multi V

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi V and is the answer not in the manual?

LG Multi V Specifications

General IconGeneral
TypeVRF (Variable Refrigerant Flow)
Compressor TypeScroll
RefrigerantR410A
Energy EfficiencyHigh
Control SystemCentralized and individual control options
Indoor UnitsMultiple types available (e.g., ceiling cassette, wall-mounted, ducted)

Related product manuals