92 Outdoor Unit
Test Run
Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan
discharge of ODU.
n Static pressure compensation dip S/W setting method
High static pressure mode : Set DIP S/W
Note
How to set the unit to high ESP :
1) Standard ESP (External Static Pressure) : 4mmH
2
O (39.2Pa)
2) High ESP (External Static Pressure) : 8mmH
2
O (78.4Pa)
The setting of dip S/W is needed. (Refer to above operating method)
Power Reset
Set the DIP S/W ON
Static pressure compensation mode setting
method
Static pressure compensation mode cancellation
method
DIP switch OFF
Power Reset
Static pressure compensation mode is set
Static pressure compensation mode is cancelled
DIP Switch Settings
Warning : Please reset Main PCB before starting this function