25
EN
Charge Using the Refrigerant Cylinder with a Siphon
This is usually applied to R32. Charge the refrigerant (gas phase) by standing the refrigerant cylinder.
Lo Hi
NOTE
Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.
Ensure that contamination of different refrigerants does not occur when using charging equipment.
Extreme care shall be taken not to overfill the refrigerant system.
Prior to recharging the system it shall be pressure tested with oxygen free nitrogen (OFN). The system shall
be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out
prior to leaving the site.
The handling of the refrigerant must comply with national regulations.