11
• For model 6000RL;
Connecting the smoke alarm on the base plate will activate the battery. Please note, the long
absence of mains power may damage the rechargeable battery. Warranty is void if the battery is
damaged. If the mains power is turned off for a long period of time, for example, if the building
is not occupied, disconnect the smoke alarm from the base plate. When mains power is turned
on, ensure the smoke alarm is then connected to the base plate. The battery may be low in new
smoke alarms, please allow up to 8 hours for the battery to fully charge. Smoke alarms may
chirp until the battery is fully charged.
• This Smoke Alarm can only interconnect with PSA Products LIFESAVER range of smoke alarms,
heat alarm and accessories. Interconnection with other brands may cause damage or result in a
shock or fire risk and void warranty.
• Due to “noise” from electromagnetic interference, up to 24 units of smoke alarms and
compatible products may be interconnected.
• There are five terminals in the supply terminal block, marked 9V, A, SW, N, LOOP. It is
important that the alarm be wired correctly to ensure correct operation. Incorrect wiring to
the smoke alarm will damage the unit and void the warranty.
• A total maximum of 250 meters (820 feet) of wire can be used in interconnecting smoke
alarms.
• Smoke Alarms can be wirelessly interconnected using a wireless baseplate Model 6000WB.
Using the wireless baseplate will not require the SW terminal to be connected.
• Smoke alarms interconnected using the wireless baseplate 6000WB can be wired to different
240VAC power circuits.
Model 6000WB