9
5. Installation
THIS SMOKE ALARM MUST BE INSTALLED BY QUALIFIED (LICENSED) ELECTRICIANS
ONLY.
Wiring Requirements
• All connections must be installed by a qualified electrician and be in accordance with the relevant
requirements of the SAA Wiring Rules AS 3000 Standards.
• The appropriate power source is 240V AC 50Hz continuous single phase sine wave current
supplied from a non-switchable circuit.
• Smoke alarms are not to be used with detector guards unless the combination (alarm and guard)
has been evaluated and found suitable for that purpose.
WARNING: This alarm cannot be operated from power derived from a square wave
or modified square wave inverter. These type of inverters are sometimes used to
supply power to the structure in off-grid installations, such as solar or wind derived
power sources. These power sources produce high peak voltages that will damage the
alarm.
Wiring instructions for Ceiling Baseplate
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING THE ALARM.
• For smoke alarms that are used as STANDALONE units, LEAVE THE SWITCH WIRE UNCONNECTED.
• When alarms are interconnected, all interconnected units must be powered from a single circuit.
• A maximum of 24 PSA LIFESAVER devices may be interconnected by hardwire.