2
CONGRATULATIONS on your purchase of a Lightstat TME. It represents
reliable, modern, electronic tempe rature control in addition to unique energy
saving features.
Features
1 Amp relay switching of up to 6 HVAC loads.
Automatic Changeover from Heating to Cooling with a 5º F deadband
between heating and cooling to prevent short cycling of equipment.
Automatic Setback of temperatures based on light sensitivity or contact
closure (model dependent).
System ON/OFF switch, and Fan switch for AUTO or ON fan operation.
PRE-CONDITION feature to pre-heat or pre-cool the building prior to
occupancy at the start of the day.
Fan control settings for Heating to allow either thermostat controlled fan
(typical of electric heat) or a limit switch controlled fan (typical of gas heat).
Auxiliary output options to permit the O/B output to be active with a call for
Heat or Cool; for heat pump reversing valve.
A1-A2 isolated dry contact outputs for night shutdown of dampers or
equipment.
Connections for using a Remote Room Sensor.
Connections for using a Supply Air Sensor.
Light Sensitivity adjustment to permit operation in bright or dim areas (model
dependent).
Stages of Heat and Cool stagger ON.
Proportional plus Integral control for accurate, even temperature control.
Factory set temperature limits to prevent overheating and overcooling.
Minimum ON and OFF time delays for compressor protection.
Field Check button to cancel time delays for checkout in the eld.
Fan harvests energy from coils.
Occupancy of less than two hours will not affect pre-conditioning timing.
Random restart after Setback or power failure.
RTU visible alarm.