This is a eld option. You might not use this with your Lightstat TME. You may
add this in the eld to an existing Lightstat TME.
Mount the Supply Air Sensor on the supply air duct securely with the probe
horizontal or downward.
Use #18 gauge 2-conductor twisted pair cable between the Lightstat TME and
the Supply Air Sensor. Supply Air Sensor is unaffected by wire runs of up to 500
feet.
Supply Air Sensor cables do not have polarity, either wire may be connected to
either terminal. Cables do not have to be shielded.
At the Lightstat TME end connect the 2-conductor cable to the two terminals
marked Remote Supply Sensor on the thermostat. At the Supply Air Sensor
end connect the two conductor cables to the wires on the Supply Air Sensor.