EasyManua.ls Logo

Lite-Puter DX-1210 - Structure

Lite-Puter DX-1210
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DX-1210/DX-1210T/DX-1220/DX-1220AF/DX-1230/DX-630/DX-640 [EUM-O] 6
DX-1210/1220/1230/630/640 meets with specifications as follows:
1. EN 55014
2. EN 61000-3-2
3. EN 61000-3-3
4. EN 50140
5. EN 61000-4-2
6. EN 61000-4-4
7. EN 61000-4-5
8. EN 61000-4-11
9. ENV 50141
2-3 Structure
Magnetic Circuit Breaker (M.C.B)
DX-1210: 10A M.C.B on each module (P-10)
DX-1210T: 10A M.C.B on each module (P-10T)
DX-1220/DX-1220AF: 25A M.C.B on each module (P-27/P-27AF)
DX-1230: 30A M.C.B on each module (P-30)
DX-630: 32A M.C.B on each module (P-30A)
DX-640: 40A M.C.B on each module (P-40A)
Thermal-controlled fan
When the internal temperature is over 34, the fans start to work 1 minute and stop 1 minute in turn;
over 37, the fans turn on continuously; over 63, all output will be stopped until the temperature
is under 60.
SSR
40A/600V (75) Itrms=40A; Itsm=350A / 60HZ , 300A / 50HZ (25) According with UL 81734
www.m-s-v.eu