SAFETYINTRODUCTION
TheLoadPower
Pleaserefertothedatawesuggestedtoensurethenormaltotalworkinghours
ofDX-610/DX-626
1. IfDX-610/DX-626isinstalledinarack,pleasemakesuretherackisairy.
Otherwisethemachinewillbecomeover-heatandresultinthe
mis-function.
2. DX-610:themax.outputofeachchannelis10A:Fortesting(DONotover30
minutes)
DX-626:themax.outputofeachchannelis20A:Fortesting(DONotover
30minutes)
3. DX-610:theoutputofeachchannelisŊ8A:Forseveralhoursuse(Theaters,
Stages)
DX-626:theoutputofeachchannelis16A:Forseveralhoursuse
(Theaters,Stages)
4. DX-610:theoutputofeachchannelis 8A:Canworkforthewholeyear
withoutswitchingoff(Hotels,Restaurants,Buildings)
DX-626:theoutputofeachchannelis 12A:Canworkforthewholeyear
withoutswitchingoff(Hotels,Restaurants,Buildings)
WorkingEnvironment
1. Temperature Under35°C
2. Ifthemachineisinstalledinarack,thenthetemperatureinsidetherack
mustbeunder45°C
3. Humidity40%---80%
SuggestedDimmingLights
Incandescentlamps,halogenlamps,lowvolthalogenlampswithballast.