28
4.3.3 Control Circuit Cable Size and Tightening Torque
Select the cable according to Table 4.3.3.1. Use crimp ferrules on the cable ends for simpler
and more reliable wiring.
Table 4.3.3.1 Cable Size and Tightening Torque
Terminal
Bare Cable
Ferrule-Type Terminal
kgf-cm(in-lbf)
Cable
Type
Suggested
Size
mm2
( AWG)
Applicable
Size
mm2
( AWG)
Suggested
Size
mm2
( AWG)
Applicable
Size
mm2
( AWG)
S1, S2, S3, S4, S5,
S6, COM, 24V,
+V,A1, AC, FM, PE
0.26 ~ 1.31
(23 ~ 16)
0.13 ~ 2.08
(26 ~ 14)
0.41 ~ 1
(17 ~ 21)
1.3 ~ 0.3
(22 ~ 16)
5.1-8.1 (4.4-7in-
lbf)
Shielded
cable, etc.
R1A, R1B, R1C
0.26 ~ 1.65
(23 ~ 15)
0.13 ~ 3.31
(26 ~ 12)
3.31
(12)
0.13 ~ 3.31
(26~12)
5.1-8.1 (4.4-7in-
lbf)
Shielded
cable, etc.
4.3.4 Ferrule-Type Terminals
Always use ferrule-type terminals with insulated sleeves. Refer to Table 4.3.3.2. for dimensions.
In addition, crimping tool CRIMPFOXZA-3 manufactured by Phoenix Contact is recommended.
Table 4.3.3.2 Ferrule-Type Terminal Models and Sizes
Cable Size
mm2 ( AWG)
Type
L
( mm)
d1
( mm)
d2
( mm)
Manufacturer
0.25 24
AI 0.25-6YE
10.5
0.8
2
Phoenix Contact
0.3422
AI 0.34-6TQ
10.5
0.8
2
Phoenix Contact
0.5 20
AI 0.56-WH
14
1.1
2.5
Phoenix Contact