Chapter 7. Usage of Various Functions
7-64
4) Scaling function (for G7F-DA2I)
Scaling is the function that changes the offset and gain value for an easy operation.
• Changing method is as below.
Scaling conversion value
800
4000
3200)value input (Digital
+
×
=
Example) Digital value 1000 input in a range of 0 ~ 20 ㎃
• Before the scaling conversion (current range 0 ~ 20mA):
5mA
4000
201000
4000
20)value input (Digital
=
×
=
×
• After the scaling conversion (current range 4 ~ 20mA):
8mA5μA1600800
4000
32001000
800
4000
3200)value input (Digital
=×=+
×
=+
×
5) Wiring
(1) Caution for wiring
• Make sure that external input signal of the mixture module of AC and analog I/O is not affected by induction noise or
occurs from the AC through using another cable.
• Wire is adopted with consideration about peripheral temperature and electric current allowance. For wire, thicker than
AWG22 (0.3 ㎟) one is recommended.
• If wire is put near to high temperature radiated device or contacted with oil for a long time, it may cause of electric
leakage so that it gets broken or miss-operation during wiring.
• Be sure to connect with care of polarity while connecting to external 24V DC power supply.
• In case of wiring with high voltage line or generation line, it makes induction failure so then it may cause of miss-
operation and out of order.
4000
0
0㎃
20 ㎃
4000
0
4㎃
20 ㎃
Resolution: 20 ㎃/4000 = 5 ㎂
Resolution: 20 ㎃/3200 = 6.25 ㎂
800