Chapter 8. Communication Functions
8-11
(4) GM7U main unit response format (NAK response)
Format name Header
Station
No.
Command
Command type
Error code
(Hex 2 Byte)
Tail Frame check
Frame (Ex.) NAK H20 R(r) SS H1132 ETX BCC
ACSII value H15 H3230 H52(72) H5353 H31313332 H03
Item Description
Error code Hex and 2 bytes (ASCII code, 4 bytes) indicate error type. For the details, see 8.1.8 Error codes.
Frame check
(BCC)
When command is lowercase(r), only one lower byte of the value resulted by adding 1 byte each
to the ASCII values from NAK to ETX is converted into ASCII and added to BCC.
(5) Example
This example assumes when 1 WORD from %MW20, and 1 WORD from %QW0.0.1 address of station No.1 are read.
H1234 is entered in %MW20, and data of H5678 is entered in %QW0.0.1.
Computer request format (PC GM7U main unit)
Format
name
Header
Station
No.
Command
Command
type
Number
of
blocks
Variable
length
Format name
Device
length
Format name
Tail
Frame
check
Frame ENQ H01 r SS H02 H05 %MW20 H08 %QW0.0.1 EOT BCC
ACSII
value
H05 H3031 H72 H5353 H3032
H3035
H254D573230
H3038
H25515730
2E302E31
H04
For ACK response after execution of command (PC GM7U main unit)
Format
name
Header
Station
No.
Command
Command
type
Number
of
blocks
Variable
length
Format
name
Device
length
Format
name
Tail
Frame
check
Frame ACK H01 r SS H02 H02 H1234 H02 H5678 ETX BCC
ACSII
value
H06 H3031 H72 H5353 H3032
H3032 H31323334
H3032 H35363738 H03
For NAK response after execution of command (PC GM7U main unit)
Format name Header Station No. Command Command type Error code Tail Frame check
Frame NAK H01 r SS Error code (2) ETX BCC
ACSII value H15 H3031 H72 H5353 Error code (4) H03
Frame check BCC is automatically operated.