Chapter 8. Communication Functions
8-30
a) Station no.: set the number of the slave or opponent station.
b) Mode: click 'send' for writing data on the slave station, or 'receive' for reading from it.
c) Size: data size for reading and writing of the master station can be specified up to 60 words.
d) Area:
Send mode Receiving mode
Indication
From Area
It is in the master station to
temporarily save the data to
be written.
It is in the slave station for the
data to be read.
To Area
It is in the slave station to write
the data.
It is in the master station to
temporarily save the data to be
read.
- When selecting %MW0, click '%MW'
and enter '0' in the blank next to it.
- When selecting %QW0.1.0, click
'%QW' and enter '0.1.0' in the blank
next to it.
3) Setting communication enable
To process 1:1 built-in communication between GM7U's, after setting communication parameter and constituting program, the user
must access the master GM7U through GMWIN, click 'connect(C)' of ‘online (O)' in menu bar, and set 'Communication Enable(L)’
of ‘Online (O)’ in the same menu bar.