Appendix 2. Flag Lists
App2-5
5) System operation status information flag lists
Keyword Type
Data
setting
range
Name Description
_CPU_TYPE UNIT 0 to 16 System type
GM1: 0, GM2: 1, (GM3: 2, GM4: 3)
(FSM: 5,6)
_VER_NUM UNIT -
O/S version
No.
System O/S version No.
_MEM_TYPE UNIT 1 to 5
Memory
module type
Type of program memory module (0: Unloading state, type: 0 to
5)
Repre-
sentative
keyword
PLC mode and
operation
status
System operation mode and operation state information
Bit 0 Local control
Operation mode change is possible only by mode change switch
or GMWIIN
Bit 1 STOP
Bit 2 RUN
Bit 3 PAUSE
Bit 4 DEBUG
CPU module operation state
Bit 5
Operation
mode change
factor
Operation mode change by mode change switch
Bit 6
Operation
mode change
factor
Operation mode change by GMWIN
Bit 7
Operation
mode change
factor
Operation mode change by remote GMWIN
Bit 8
Operation
mode change
factor
Operation mode change by communications
Bit 9
STOP by
STOP function
Operation in the RUN mode is stopped by STOP function after the
scan has finished
Bit 10 Force input Input junction force On/Off is being executed.
Bit 11 Force output Output junction force On/Off is being executed
Bit 12
STOP by
ESTOP
function
Operation in the RUN mode is directly stopped by ESTOP
function.
Bit 13 - -
Bit 14
During
monitoring
External monitoring is being executed for programs or variables
_SYS_STATE WORD
Bit 15
Remote mode
ON
Operation in the remote mode
Repre-
sentative
keyword
GMWIN
connection
state
Connection state between CPU module and GMWIN
Bit 0
Local GMWIN
connection
Local GMWIN connection state
Bit 1
Remote
GMWIN
connection
Remote GMWIN connection state
_GMWIN_CNF BYTE
Bit 2
Remote
communicatio
ns connection
Remote communications connection state
* Marked flags can be used while the RTC option module is in use.