EasyManua.ls Logo

LS Industrial Systems GLOFA G7M-DR60U - RTD Input Module

LS Industrial Systems GLOFA G7M-DR60U
367 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7. Usage of Various Functions
7-70
7.2.5 RTD input module
1) Performance specification
The performance specifications of the RTD input module are following.
Item Specifications
Connectable RTD
Pt 100 (JIS C1640-1989, DIN 43760-1980)
JPt100 (KS C1603-1991, JIS C1604-1981)
Temperature input
range
Pt 100: -200 ~ 600 (18.48 to 313.59 Ω)
JPt100: -200 ~ 600 (17.14 to 317.28 Ω)
Digital output
Digital conversion value: 0 ~ 4,000
Detected temperature value: -2000~6000(one digit after point X 10)
Burn out detection
Three wires at every channel has detection function respectively
A
ccurac
y
±0.5%
[
Full Scale
]
Maximum conversion
speed
40 scan / all channel
Temperature input point 4 channel / 1 module
No. of module
installation
Max. 3 modules
Insulation
Photo-coupler insulation between the input terminal and the PLC power
supply (non-insulation between channels)
Connection terminal
block
2 of 8 points terminal
Current consumption
25
Voltage DC 21.6 26.4V
External power
supply
Current
70
Weight 240g
2) Names of parts and functions
No.
Name Function
RUN LED
Indicates the operating status of G7F-
RD2A.
RTD input
terminal
Terminal which connects Pt100 or JPt100
External power
input terminal
Supply external voltage DC 24V
Extension cable
This cable is used to connect while RTD
input module is used.
Extension cable
connector
The connector connects extension cable
when extended module is used.
24V
B
A
b
·
B
A
b
·
A
b
B
A
b
24
G
G7F-RD2A
PROGRAMMABLE
LOGIC
CONTROLLER
CH2
CH3
Input
CH0
CH1
PWR
B