iG5A
10
Standard Specifications
1) Means average braking torque during Decel to stop of a motor.
2) Refer to Chapter 16 of user’s manual for DB resistor specification.
Over voltage, Under voltage, Over current, Ground fault current detection, Inverter overheat,
Motor overheat, Output phase open, Overload protection, Communication error,
Loss of speed command, Hardware fault, Fan trip
V/F, Sensorless vector control
Linear, Squared, User V/F
150% per 1 min.
Manual/Auto torque boost
20%
150% when using optional DB resistor
Digital command: 0.01Hz
Analog command: 0.06Hz (Max. freq.: 60Hz)
Digital command: 0.01% of Max. output frequency
Analog command: 0.1% of Max. output frequency
Trip
Alarm
Momentary power loss
Operation mode
Frequency setting
Operation features
Dynamic
braking
Input
Output
Max. braking
torque
Max. Duty
Open collector
terminal
Multi-function relay
Analog output (AM)
IP 20, NEMA Type 1 (Optional)
-10~50
-20~65
Below 90% RH (No condensation)
Below 1,000m, 5.9m/sec
2
(0.6G)
70~106 kPa
Protected from corrosive gas, Combustible gas, Oil mist or dust
1)
2)
Keypad/ Terminal/ Communication option/ Remote keypad selectable
PID, Up-down, 3-wire
NPN/PNP selectable
0~10Vdc (less than 10mA): Output freq, Output current, Output voltage, DC link selectable
FWD/REV RUN, Emergency stop, Fault reset, Jog operation, Multi-step Frequency-High, Mid, Low,
Multi-step Accel/Decel-High, Mid, Low, DC braking at stop, 2nd motor select, Frequency UP/Down,
3-wire operation, External trip A, B, PID-Inverter (V/F) operation bypass,
Option-inverter (V/F) operation bypass, Analog Hold, Accel/Decel stop
Analog: 0~10V, -10~10V, 0~20mA
Digital: Keypad
Fault output and
inverter status output
Less than DC 24V, 50mA
(N.O., N.C.) Less than AC 250V, 1A; Less than DC 30V, 1A
Stall prevention, Overload
Below 15 msec.: Continuous operation (Should be within rated input voltage, rated output power.)
Above 15 msec.: Auto restart enable
Protection degree
Ambient temp
Storage temp
Humidity
Altitude/Vibration
Atmospheric pressure
Location
Control method
Frequency setting resolution
Frequency accuracy
V/F pattern
Overload capacity
Torque boost
Multi-function
terminal
P1~P8
Environ
ment
Control
Protective
function
Operation

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LS Industrial Systems STARVERT iG5A and is the answer not in the manual?

LS Industrial Systems STARVERT iG5A Specifications

General IconGeneral
BrandLS Industrial Systems
ModelSTARVERT iG5A
CategoryInverter
LanguageEnglish

Related product manuals