Easy Start Guide
9. How to connect and configure a Potentiometer
for remote speed control
LS Industrial Systems SV-iC5
Page 10
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission.
©
2
1
3
VR V1 CM
213
Parameter
Description
How to set
Frq
Speed Command Source
Set to to enable 0-10V via 10kOhm Potentiometer3
9.1 Parameters to change in the Drive Group
Press left/right to find 0.0 then up/down to find parameter number
If the integrated speed control dial is
unsuitable for the application, a remote
Potentiometer can be used instead.
This provides the benefit of allowing motor
speed to be controlled from a more convenient
location such as a cabinet door (if the iC5 is
cabinet-mounted) or on the machine itself.
A Potentiometer of rating should be
used.
The number of turns depends on the
application but both single turn and ten turn
Potentiometers are available from The Inverter
Drive Supermarket at InverterDrive.com.
10kOhm
9.2 Connecting the Potentiometer
A wiring diagram is shown in the illustration
opposite. The most important connection at
the Potentiometer end is the centre terminal or
“wiper”.
The wiper will output a variable voltage
between 0 and 10 volts and should be
connected to the V1 terminal at the Inverter
end. It is this voltage which provides the speed
signal with 0V being slowest and 10V fastest.
The default output frequency at 0V is 0.5Hz. To
change this, edit Parameter F25.
The default output frequency at 10V is 50Hz.
To change this, edit Parameter F26.
If the rotation of the Potentiometer is the
opposite to that required (ie. turn anti-
clockwise to increase speed instead of
clockwise) reverse connections VR and CM.
Use shielded SY cable between Potentiometer
and Inverter and ensure that the cable screen
is earthed at the green earth terminal on the
Inverter.
Screen to
Earth Terminal
iC5 I/O
Terminal
Blocks
10kOhm
Potentiometer
SY Cable

Related product manuals