LS Industrial Systems SV-iC5
Easy Start Guide
1. Power and Motor Connections
Page 2
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission.
©
L1 L2 NPP1 U V W
MotorPower
Live
Neutral
Earth
Phase
Phase
Phase
Earth
Notes:
The illustration above is based on 1.5kW and
2.2kW models. The terminal layout for 0.37kW
and 0.75kW models is slightly different.
The smaller green earth terminals are not part
of the main termal block.
The order of the three phases determines the
direction the motor turns.
Important:
Do NOT connect Neutral to the terminal
marked N.
Use screened SY cable between the Inverter
and Motor to minimise electromagnetic
interference.
Ensure the motor cable screen is earthed at
the motor end.
Before commencing, confirm that the iC5 and all
cables are completely isolated from the power
supply, have been isolated for at least 5 minutes
and that the motor is not turning.