Safety Instructions
i
Thank you for purchasing LS Variable Frequency Drives!
SAFETY INSTRUCTIONS
To prevent injury and property damage, follow these instructions during the
installation and operation of the inverter.
Incorrect operation due to ignoring these instructions may cause harm or damage.
The following symbols are used throughout the manual to highlight important
information.
The meaning of each symbol in this manual and on your equipment is as
follows.
This is the safety alert symbol.
Read and follow instructions carefully to avoid a dangerous situation.
This symbol alerts the user to the presence of “dangerous voltage” inside the
product that might cause bodily harm or electric shock.
This manual should be placed in a location where it can be accessed by users.
This manual should be given to the person who actually uses the inverter and is
responsible for its maintenance.
DANGER
WARNING
CAUTION
This symbol indicates the possibility of
death or serious injury.
This symbol indicates the possibility of
damage to the inverter or other components.
This symbol indicates death or serious injury can
occur if you do not follow instructions.
Question and Answer IconNeed help?

Do you have a question about the LSIS SV110IP5A-4NE and is the answer not in the manual?

Overview

This document describes the LS Variable Frequency Drives (VFDs), specifically the SV-iP5A series, providing essential information for their installation, operation, and maintenance.

Function Description:

The SV-iP5A series VFDs are designed to control and monitor three-phase AC asynchronous (Induction Motor) motors, enabling precise speed and torque adjustments. They are suitable for various industrial applications, including fan, pump, and HVAC systems, as well as multi-motor control. The VFDs convert incoming AC power into a variable frequency and voltage output, allowing for efficient motor operation and energy saving. They support both V/F control and Sensorless Vector control modes, with auto-tuning capabilities to maximize motor performance. The VFDs can be controlled via a keypad, external control terminals, or through RS485 communication, offering flexibility in integration with PLC or other master control systems.

Important Technical Specifications:

The SV-iP5A series covers a wide range of power ratings and voltage classes. For the 200-230V Class, models range from 0.75kW (1HP) to 30kW (40HP) for fan/pump loads and 0.4kW (0.5HP) to 22kW (30HP) for general loads. Output current ranges from 5A to 115A for fan/pump loads and 2.5A to 84A for general loads, with 110% overload for 1 minute (Normal Duty) and 150% overload for 1 minute (Heavy Duty) respectively. For the 380-480V Class, models range from 0.75kW (1HP) to 450kW (700HP). Output current for fan/pump loads ranges from 2.5A to 877A, and for general loads, from 1.25A to 731A, with similar overload capacities. The VFDs operate within a frequency range of 0.01 to 120 Hz. Input voltage tolerance is -15% to +10% for three-phase 200-230V and 380-480V systems. Protection degree is IP20 / UL Type1 for standard models and IP00 / UL Open for higher power models, with options for UL Enclosed Type 1. Common specifications include:

  • Cooling method: Forced air cooling (Self-cooling for below 1.5kW).
  • Short Circuit Rating: 65kA, suitable for use on a circuit capable of delivering not more than 100,000 RMS Symmetrical amperes, 240V (or 480V) maximum.
  • Agency Approvals: UL and cUL listed, CE marked.
  • Control Methods: V/F, Sensorless Vector, Slip Compensation, Easy Start Selectable.
  • Frequency Setting Resolution: 0.01 Hz (Digital, below 100 Hz), 0.1 Hz (Digital, over 100 Hz), 0.01 Hz / 60 Hz (Analog).
  • Frequency Accuracy: 0.01% (Digital), 0.1% (Analog) of Max. Output Frequency.
  • Overload Capacity: 110% for 1 minute, 120% for 1 minute (at 25°C ambient).
  • Torque Boost: Manual (0-15% settable) or Auto.
  • Operation Method: Keypad, Terminal, or Communication.
  • Accel/Decel Time: 0.1 to 6,000 seconds, with Linear, U-Curve, S-Curve patterns.
  • Ambient Temperature: -10°C to 50°C (14°F to 122°F), with derating above 40°C.
  • Storage Temperature: -20°C to 65°C (-4°F to 149°F).
  • Ambient Humidity: Less than 90% RH Max. (Non-Condensing).
  • Altitude: Below 1,000m (3,300ft).
  • Application Site: Pollution degree 2, no corrosive gas, combustible gas, oil mist, or dust.

Usage Features:

The VFDs offer a user-friendly LCD keypad for programming and monitoring, displaying up to 32 alphanumeric characters. The keypad allows for easy navigation through seven program groups (DRV, FU1, FU2, I/O, EXT, COM, APP) to adjust various parameters.

  • Easy Start Operation: Activated by pressing the STOP key for 2-3 seconds, pre-setting drive mode to V/F and reference frequency to JOG.
  • Control via Terminal: Supports external control signals for run/stop commands (FX/RX terminals) and frequency setting (V1, V1S, I terminals).
  • Control via Keypad: Allows direct control and frequency setting from the keypad.
  • Parameter Groups: Parameters are organized into logical groups for efficient configuration:
    • Drive Group (DRV): Command frequency, accel/decel time, basic functions.
    • Function 1 Group (FU1): Max frequency, torque boost, protection settings.
    • Function 2 Group (FU2): Frequency jumps, max/min frequency limits, auto-tuning.
    • Input/Output Group (I/O): Programmable digital input/output, analog command, sequence configuration.
    • Application Group (APP): PID control, Multi-Motor Control (MMC), 2nd motor operation.
  • Advanced Functions: Includes PID control for process regulation, Ext PID for external feedback, Pre PID for smooth starts, and MMC for integrated system control.
  • Multi-speed and Jog Operation: Up to 18 speeds can be set, including jog operation.
  • Energy-saving Operation: FU1-51 [Energy Save Level] tunes output voltage for constant speed operation, suitable for fan/pump applications.
  • RS485 Communication: Enables control and monitoring via PC or PLC, supporting multi-drop link systems with up to 31 drives. Baud rates from 1200 bps to 19200 bps are selectable.

Maintenance Features:

Routine and periodic inspections are crucial for maintaining the VFD's performance and longevity.

  • Precautions: Always disconnect power and wait at least 10 minutes for capacitors to discharge (DC link voltage below 30VDC) before maintenance. Use a rectifier voltage meter for accurate output voltage measurements.
  • Routine Inspection: Check installation conditions, cooling, abnormal vibrations or noise, and heating/discoloration.
  • Periodic Inspection:
    • Inspect for loose bolts, nuts, or rust; tighten or replace as needed.
    • Clean cooling fan and PCB boards using an air gun to remove deposits.
    • Check connectors for abnormalities.
    • Verify cooling fan operation and capacitor condition.
  • Troubleshooting: The VFD displays fault codes (e.g., Over Current, Ground Fault, Over Voltage, Over Load, Over Heat, E-Thermal, Ext. Trip, Low Voltage, IGBT Short, Output/Input Phase Open, HW-Diag, COM Error, NTC open, Lost cmd, Fuse Open, Keypad FLT) on DRV-12. The last 5 faults are saved in FU2-01 to FU2-05.
  • Fault Reset: Faults can be reset via the keypad [RESET] key, RST-CM terminals, or by cycling input power.
  • Power Components Check: Detailed instructions are provided for checking diode and IGBT modules (for 5.5-30kW and 37-90kW models) using a tester after power disconnection and discharge.
  • Megger/Withstanding Voltage Test: Perform megger tests only on the main circuit (not control circuit) with DC 500V megger after disconnecting inverter wiring. Do not apply test voltage to the inverter.
  • Parts Replacement: Recommended replacement intervals for cooling fans (2-3 years) and electrolytic capacitors (5 years) are provided. Capacitors should be replaced if their initial value drops by 15% or more. Relays should be replaced as needed.
  • Single-Phase Input Considerations: When using single-phase input, derating of the VFD's power rating is necessary due to increased DC bus ripple and higher input currents/harmonics. An AC reactor is always required. Specific wiring configurations for single-phase input are detailed.