EasyManuals Logo

LSIS SV220iG5A-4 User Manual

LSIS SV220iG5A-4
181 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #77 background imageLoading...
Page #77 background image
7-1
CHAPTER 7 - BASIC FUNCTIONS
7.1 Frequency mode
z Keypad Frequency setting 1
Group Code Parameter Name Setting Range Initial Unit
Drive group 0.00 [Frequency Command] - 0 ~ 400 0.00 Hz
Frq [Frequency mode] 0
0 ~ 8 0
Set Frq – [Frequency mode] to 0 {Frequency setting via Keypad 1}.
Set the desired frequency in 0.00 and press the Prog/Ent (z) key to enter the value into
memory.
The value is settable less than F21 – [Max frequency].
When remote keypad is connected, keypad keys on the body are deactivated.
z Keypad Frequency setting 2
Group Code Parameter Name Setting Range Initial Unit
Drive group 0.00 [Frequency Command] - 0 ~ 400 0.00 Hz
Frq [Frequency mode] 1
0 ~ 8 0
Set Frq – [Frequency mode] to 1{Frequency setting via Keypad 2}.
In 0.00, frequency is changed upon pressing the Up (S)/Down (T) key. In this case,
UP/Down keys serve as a potentiometer.
The value is settable less than F21 – [Max frequency].
When remote keypad is connected, keypad keys on the body are deactivated.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS SV220iG5A-4 and is the answer not in the manual?

LSIS SV220iG5A-4 Specifications

General IconGeneral
BrandLSIS
ModelSV220iG5A-4
CategoryInverter
LanguageEnglish

Related product manuals