26
N31U User manual
Designations used in the drawing:
AL_L – corresponds to PrL setting and determines the alarm state change
lower threshold.
AL_H – corresponds to PrH setting and determines the alarm state
change upper threshold.
Note: It is important to keep in mind when conguring the alarms that
the entered threshold values should match the dependency AL_L <
AL_P. Otherwise the dependency will disable the alarms.
An additional alarm function makes it possible to dene an alarm activation
and deactivation delay. The user can dene how long the alarm event must
last before the alarm relay contacts are switched on and the minimum time of
the alarm event end before the relay contacts are switched o󰀨. Alarm delays
prevent false alarms caused by a short-term change of the measuring value,
e.g. opening the door to the cold store.
The alarm event could be registered if the alarm memory is enabled.
Fig. 12: Alarm types: a) n-on; b) n-o; c) o; f) on.