30
N31U User manual
5.5.4.1 Registers 4000 – 4024
16-bit readout and write conguration registers.
Address Permissible
values
Default Description
Measurement, display and protection of conguration
4000 0...15 13
Type of measuring input Type of connected input signal
Value Type of signal / range/ sensor
0 PT100
1 PT1000
2
Resistance, range 400
3
Resistance, range 4000
4 Thermocouple type E
5 Thermocouple type J
6 Thermocouple type K
7 Thermocouple type N
8 Thermocouple type R
9 Thermocouple type S
10 60 mV – voltage measurement
11 150 mV – voltage measurement
12 300 mV – voltage measurement
13 10 V – voltage measurement
14 0...20 mA – current measurement
15 4...20 mA – current measurement
4001 1...600 10 Averaging - number of the samples averaged for one measurement. Sampling rate
100 ms (200 ms for the RTD sensors in 3-wire system). The parameter determines
time of a single measurement.
4002 1...3600 1 Number of single measurements averaged sing the moving window method.
4003 0, 1 0 Enable a manual compensation of the terminals resistance or temperature measure-
ment. The value 0 enables an automatic compensation.
4004 0...5 0
Mathematical functions used for the measuring value.
Value Description
0 Disabled.
1 Square of the measuring quantity.
2 Square root of the measuring quantity.